Moulded Case Circuit Breakers Explained

21 Oct.,2024

 

Moulded Case Circuit Breakers Explained

As installed system capacity continues to increase in the Australian PV market, it is valuable for system designers and installers to understand the mechanisms behind moulded case circuit breakers, and the meaning behind their ratings.

If you are looking for more details, kindly visit our website.

A moulded case circuit breaker (MCCB) is a type of electrical protection device that is used to protect the electrical circuit from excessive current, which can cause overload or short circuit. With a current rating of up to A, MCCBs can be used for a wide range of voltages and frequencies with adjustable trip settings. These breakers are used instead of miniature circuit breakers (MCBs) in large scale PV systems for system isolation and protection purposes.

How the MCCB operates

The MCCB uses a temperature sensitive device (the thermal element) with a current sensitive electromagnetic device (the magnetic element) to provide the trip mechanism for protection and isolation purposes. This enables the MCCB to provide:

  • Overload Protection,
  • Electrical Fault Protection against short circuit currents, and
  • Electrical Switch for disconnection.

Overload Protection

Overload protection is provided by the MCCB via the temperature sensitive component. This component is essentially a bimetallic contact: a contact which consists of two metals that expand at different rates when exposed to high temperature. During the normal operating conditions, the bimetallic contact will allow the electric current to flow through the MCCB. When the current exceeds the trip value, the bimetallic contact will start to heat and bend away due to the different thermal rate of heat expansion within the contact. Eventually, the contact will bend to the point of physically pushing the trip bar and unlatching the contacts, causing the circuit to be interrupted.

The thermal protection of the MCCB will typically have a time delay to allow a short duration of overcurrent which is commonly seen in some device operations, such as inrush currents seen when starting motors. This time delay allows the circuit to continue to operate in these circumstances without tripping the MCCB.

Electrical Fault Protection against short circuit currents

MCCBs provides an instantaneous response to a short circuit fault, based on the principle of electromagnetism. The MCCB contains a solenoid coil which generates a small electromagnetic field when current passes through the MCCB. During normal operation, the electromagnetic field generated by the solenoid coil is negligible. However, when a short circuit fault occurs in the circuit, a large current begins to flow through the solenoid and, as a result, a strong electromagnetic field is established which attracts the trip bar and opens the contacts.

Electrical Switch for disconnection

In addition to tripping mechanisms, MCCBs can also be used as manual disconnection switches in case of emergency or maintenance operations. An arc can be created when the contact opens. To combat this, MCCBs have internal arc dissipation mechanisms to quench the arc.

Deciphering MCCB Characteristics and Ratings

MCCB manufacturers are required to provide the operating characteristics of the MCCB. Some of the common parameters are explained below:

Rated Frame Current (Inm) The maximum current that the MCCB is rated to handle. This rated frame current defines the upper limit of the adjustable trip current range. This value determines the breaker frame size. Rated Current (In): The rated current value determines when the MCCB trips due to overload protection. This value can be adjusted, to a maximum of the rated frame current. Rated Insulation Voltage (Ui) This value indicates the maximum voltage which the MCCB can resist in lab conditions. The rated voltage of MCCB is typically lower than this value to provide a safety margin. Rated Working Voltage (Ue) This value is the rated voltage for the continuous operation of MCCB. It is normally the same as or close to the system voltage. Rated Impulse Withstand Voltage (Uimp) This value is the transient peak voltage the circuit breaker can withstand from switching surges or lightning strikes. This value determines the ability of the MCCB to withstand transient over-voltages. The standard size for impulse testing is 1.2/50µs. Operating Short Circuit Breaking Capacity (Ics) This is the highest fault current that the MCCB can handle without being permanently damaged. MCCBs are generally reusable after fault interruption operation provided they do not exceed this value. The higher the Ics, the more reliable the circuit breaker. Ultimate Short Circuit Breaking Capacity (Icu) This is the highest fault current value that the MCCB can handle.

If the fault current exceeds this value, the MCCB will be unable to trip. In this event, another protection mechanism with a higher breaking capacity must operate. This indicates the operation reliability of the MCCB.

It is important to note that if the fault current exceeds Ics but does not exceed Icu, the MCCB can still remove the fault, but may be damaged and require replacement.

Mechanical Life This is the maximum number of times the MCCB can be operated manually before it fails. Electrical Life This is the maximum number of times the MCCB can trip before it fails.

Sizing the MCCB

MCCBs in an electrical circuit should be sized according to the circuit&#;s expected operating current and possible fault currents. The three main criteria while selecting MCCBs are:

  • The rated working voltage (Ue) of the MCCB should be similar to the system voltage.
  • The trip value of the MCCB should be adjusted according to the current drawn by the load.
  • The breaking capacity of the MCCB must be higher than the theoretical possible fault currents.

Types of MCCB

Type of MCCB Operating Current Operating Time Application Suitability Surge Current Installation Location Type B Trips between 3 and 5 times rated current (In) 0.04-13 seconds Domestic applications (lighting and resistive elements) Resistive load application Low Sub feeder of Distribution board Type C Trips between 5 and 10 times rated current (In) 0.04-5 seconds Commercial or industrial applications Inductive load applications Moderate At incoming/outgoing of Distribution Board Type D Trips between 10 and 20 times rated current (In) 0.04-3 seconds Commercial or industrial applications Inductive &#; capacitive load applications (Pumps, motor, large winding motors etc.) High At incoming of Distribution Board/Panels Type K Trips between8 and 12 times rated current (In) 0.04-5 seconds Industrial applications Inductive and motor loads with high inrush currents. High At incoming of Distribution Board/Panels Type Z Trips between 2 and 3 times rated current (In) 0.04-5 seconds Highly sensitive to short circuit and are used for protection of highly sensitive devices such as semiconductor devices Medical instruments Very low At sub feeder of Distribution board for IT equipment.

Figure 1: Trip curve of type B, C, and D MCCBs

MCCB Maintenance

MCCBs are subjected to high currents; therefore maintenance of MCCBs is critical for reliable operation. Some of the maintenance procedures are discussed below:

1. Visual Inspection

During the visual inspection of a MCCB, it is important to look out for deformed contacts or cracks in casing or insulation. Any burn marks on contact or casing should be treated with caution.

2. Lubrication

Some MCCBs require adequate lubrication to ensure the smooth operation of the manual disconnection switch and internal moving parts.

3. Cleaning

The dirt deposits on MCCBs can deteriorate the MCCB components. If the dirt includes any conducting material it may create a path for current and cause an internal fault.

4. Testing

There are three main tests that are carried out as a part of maintenance procedure of a MCCB.

Insulation Resistance Test:

The tests for a MCCB should be conducted by disconnecting the MCCB and testing the insulation between the phases and across the supply and load terminals. If the measured insulation resistance is lower than the manufacturer&#;s recommended insulation resistance value then the MCCB will not be able to provide adequate protection.

Contact Resistance:

This test is conducted by testing the resistance of the electrical contacts. The measured value is compared to the value specified by the manufacturer. Under normal operating conditions, contact resistance is very low since MCCBs must allow operating current through with minimum losses.

Tripping Test:

This test is conducted by testing the response of the MCCB under simulated overcurrent and fault conditions. Thermal protection of the MCCB is tested by running a large current through the MCCB (300% of rated value). If the breaker fails to trip, it is an indication of failure of thermal protection. The test for magnetic protection is conducted by running short pulses of very high current. Under normal conditions, magnetic protection is instant. This test should be conducted at the very end as high currents increase the temperature of contacts and insulation, and this may alter the results of other two tests.

Conclusion

The correct selection of MCCBs for the required application is key to providing adequate protection in sites with high power equipment. It is also important to carry out maintenance actions at regular intervals and each time after trip mechanisms have been activated to ensure the safety of the site is maintained.

What Is a Molded Case Circuit Breaker (MCCB)?

    Molded Case Circuit Breakers(MCCB) are electrical protection gadgets that can be used with a wide range of voltages to protect your appliances and electrical circuit from excessive current. MCCBs, as they are commonly known, have adjustable trip settings and can hold as much as 2,500 amps in current ratings. They are also used with frequencies that are 50 and 60 Hz and have the following 3 functions:

    Due to the fact that they can handle especially high currents, molded case circuit breakers are often used with applications that are heavy duty. Some of the applications of MMCB are as follows:

  1. Protecting Generators

    They usually produce hundreds of amps in output and require expensive gen-sets. MCCBs, which can handle the current ratings, provide the protection needed.

  2. Protecting Electric Feeders

    If you are using feeder circuits to distribute electric current, they can carry hundreds of amps. In some instances, you may also have additional circuits that will need trip settings. MCCBs come in handy in both the situations.

  3. Welding Machines

    It is possible to have some welding applications that draw very high currents thus needing MCCBs since miniature circuit breakers cannot handle the high currents.

  4. Protecting Capacitor Banks

    These are used to correct power factors in industrial and commercial electrical systems. If the currents they draw are very high, MCCB protection becomes a necessity to reduce currents.

  5. Protecting Motors

    Electric motors also need to be adequately protected and MCCBs do this work very well. Inrush current may need to be adjusted, providing the necessary overload protection without tripping.

  6. Adjustable trip settings for applications with low currents

    With competitive price and timely delivery, Sager sincerely hope to be your supplier and partner.

    MCCBs, even though they are known to be used with high current applications can also be used with low current ones. They provide adjustable trip settings.

  7.  

    How to test a MCCBs?

    Testing Insulation Resistance

    This test is done to ensure that you get reliable protection. It requires you to disconnect the MCCB so that you can test the insulation across the load terminals, supply terminals and between phases. If the insulation resistance is found to be lower than the manufacturers&#; recommended value, then the protection is not adequate.

    Testing Contact Resistance

    Usually, this is a rather low value because the MCCB needs to allow current to pass through even when it has a low voltage. You will need to test the resistance of electrical contact and then compare your findings with the manufacturer&#;s recommendations.

    The Tripping Test

    You will need to simulate a fault or overcurrent and then observe how the MCCB responds. You want to carry out this test last since the MCCB will heat up due to the high current. It is a two-part test which is conducted in the following sequence:

    • Thermal Protection

      This is where you use an over-current about 300 percent above the rated value. Ideally, the breaker should trip correctly. If it doesn&#;t then it is failing in thermal protection.

    • Magnetic Protection

      Here you would want to simulate a fault by sending pulses of current that are very high. The pulses need to be very short since a fault can be very dangerous. Magnetic protection tends to be instant and these can be handled well by the application.

     

    Maintaining MCCBs

    It is important to periodically provide maintenance for your molded case circuit breakers if they are to provide reliable protection. Some of the maintenance procedures necessary include the following:

    • A visual inspection
    • Cleaning
    • Lubrication
    • Testing as explained in the section above

     

    Carrying Out a Visual Inspection

    This simply means checking for any signs that the MCCB has been damaged. Some of the signs that indicate damage include the following:

    • Electric arcing indicated by casing or contact burns
    • Signs of overheating such as insulation and casing cracks or deformed contacts

    There are MCCBs that are sealed at the factory and others that can be opened. If yours can be opened, take a look at its internal components.

     

    Cleaning

    Dirt accumulated over time, can cause the components of the MCCB to deteriorate. Additionally, dirt can conduct electricity and cause a fault internally. Use a vacuum cleaner to get rid of the dirt. With the dirt removed, even your visual inspection becomes much easier.

     

    Lubrication

    As mentioned above, there are MCCBs that are sealed at the factory and others that can be opened. Lubrication is only applicable to those that can be opened. It ensures that moving parts and the manual disconnection switch work properly. This is a critical factor where faults are concerned.

     

    Conclusion

    High current applications need to have molded case circuit breakers. Getting the right size and ensuring that proper maintenance is carried out means that you will have a reliable MCCB that is also safe. To find out more about MCCBs, contact us here and we will be happy to give you more information.

    D&F Liquidators has been serving the electrical construction materials needs for more than 30 years. It is an international clearinghouse, with 180,000 square facility located in Hayward, California. It keeps an extensive inventory of electrical connectors, conduit fitting, circuit breakers, junction boxes, wire cable, safety switches etc. It procures its electrical materials supplies from top-notch companies across the globe. The Company also keeps an extensive inventory of electrical explosion proof products and modern electrical lighting solutions. As it buys materials in bulk, D&F is in a unique position to offer a competitive pricing structure. Besides, it is able to meet the most discerning demands and ship material on the same day.

    The company is the world’s best mccb supplier supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.