This chart is useful for finding the correct wire size for any voltage, length, or amperage flow in any AC or DC circuit. For most DC circuits, particularly between the PV modules and the batteries, we try to keep the voltage drop to 3% or less. Theres no sense using your expensive PV wattage to heat wires. You want that power in your batteries!
If you want to learn more, please visit our website.
Note: This formula doesnt directly yield a wire gauge size, but rather a VDI number, which is then compared to the nearest number in the VDI column, and then read across to the wire gauge size column.
1. Calculate the Voltage Drop Index (VDI) using the following formula:
VDI = AMPS x FEET ÷ (% VOLT DROP x VOLTAGE)
2. Determine the appropriate wire size from the chart below.
For more information, please visit Mingda.
Example: Your PV array consisting of four 75W modules is 60 feet from your 12-volt battery. This is actual wiring distance, up pole mounts, around obstacles, etc. These modules are rated at 4.4 amps x 4 modules = 17.6 amps maximum. Well shoot for a 3% voltage drop. So our formula looks like:
VDI =17.6 x 60
Looking at our chart, a VDI of 29 means wed better use #2 wire in copper, or #0 wire in aluminum. Hmmm. Pretty big wire. What if this system was 24-volt? The modules would be wired in series so each pair of modules would produce 4.4 amps. Two pairs x 4.4 amps = 8.8 amps max.
Chart developed by John Davey and Windy Dankoff. Used with permission.